Features |
Technical Specification |
|
General |
IT Available Space |
25U~100U |
IT Load Capacity |
2.4kW~16kW |
|
Number of Cabinets |
1~4 (Up to 10 Cabinets) |
|
Area Coverage |
0.7* Number of Cabinets ㎡ |
|
Environmental Adaptability |
Ambient Temperature |
0~40℃ |
Relative Humidity |
5%~95% |
|
Elevation |
0~3000m |
|
Degree of Protection |
IP50 |
|
Structural System |
Cabinet Dimension |
600mm*1200mm*2050mm(W*D*H) |
Equipment Installation Depth |
800 mm |
|
Cabling Mode |
Above or Below |
|
Airtight Container |
Closed Hot and cold Aisle |
|
Power Supply & Distribution System |
Power |
220V, 380VAC@50Hz |
Power Supply Path |
Single/Dual |
|
UPS |
3, 6, 10, 15, 20kVA |
|
Battery Type |
Lead Acid Battery |
|
Backup time |
15min, 30min, 1h, 2h |
|
PDU |
Input: 16A single phase, 32A single phase Output: 20 * C1 3 + 4 * C19 |
|
Cooling System |
Cooling capacity |
3.5kW, 6.5kW |
Installation Mode |
Rack Type |
|
Refrigerant |
Eco Friendly refrigerant R410A |
|
Emergency cooling |
Rear door automatically opens for ventilation |
|
Intelligent Management System |
Host Monitor |
1U rack type |
Monitoring objects |
UPS, distribution box, air conditioning, temperature and humidity, smoke, water leakage, Magnetic Door, Access |
|
Notification Mode |
SMS、Email、APP、DCIM |
|
North bound Interface Protocol |
SNMP |
|
South Bound Interface Protocol |
Modbus |